(1) Site wiring fault function is only for single phase bypass input. If the utility power is IT
system, the site wiring fault function should be disabled.
HE voltage high limit 5%~20% 10%
HE frequency low limit -10%~-5% 5%
HE frequency high limit 5%~10% 5%
Dual input function [Enabled], [Disabled] Disabled
Output
UPS Mode
[Normal mode], [HE mode],
[CVCF mode]
Normal mode
Output voltage [220V], [230V], [240V] 230V
Output frequency [Auto detection], [50Hz], [60Hz]
Auto
detection
ESS function [Enabled], [Disabled] Disabled
Auto bypass [Enabled], [Disabled] Enabled
Auto restart [Enabled], [Disabled] Enabled
Short circuit auto clear [Enabled], [Disabled] Disabled
Overload pre-alarm 50%~105% 105%
Battery
DC Start [Enabled], [Disabled] Enabled
Battery Auto Test [Every cycle] [Disabled] Every cycle
Deep discharge protection [Enabled], [Disabled] Enabled
Low bat warning 0%~100% 0%
Low remaining time warning
0-999min 0min
Restart battery level 0~100% 0%
Charger current [1-13A] for 10-20K Default 1.8A
External battery setting
[Auto detection], [Manual AH
setting]
Manual AH setting: [9-300AH]
[Auto
detection]
/
Communi
cation
Dry in
[No function] [Start UPS]
[Remote shut down]
[Maintenance bypass]
No function
Dry out
[load powered] [on battery]
[Low battery] [No Battery]
[Bypass] [ups OK]
load powered
Password
Control Menu password
[Enabled], [Disabled] Enabled
Setting Menu password
[Enabled], [Disabled] Enabled
Change Password
Old password
New password
Confirm password
[4732]