Product safety
The UPS connection instructions and operation described in the manual
must be followed in the indicated order.
UPS enclosure IP rating IP20.
CAUTION - To reduce the risk of fire, the unit connects only to a circuit
provided with branch circuit overcurrent protection.
The upstream circuit breaker for Normal AC/Bypass AC must be easily
accessible. The unit can be disconnected from AC power source by
opening this circuit breaker.
An additional AC contactor is used for back feed protection and must
comply with IEC/EN 62040-1 (the creep age and clearance distances shall
meet the basic insulation requirements for pollution degree 2).
Disconnection and overcurrent protection devices shall be provided by
others for permanently connected AC input (Normal AC/Bypass AC) and
AC output circuits.
Check that the indications on the rating plate correspond to your AC
powered system and to the actual electrical consumption of all the
equipment to be connected to the system.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near
the equipment and shall be easily accessible.
Never install the system near liquids or in an excessively damp
environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry
place.
The admissible storage temperature range is -25°C to +55°C without
battery (-15°C to +40°C with battery).
TN-S/IT/TN-C/TT of electrical supply system may be connected by UPS.
This UPS may be provided with a maximum of 6 extension battery
cabinets or equivalent.