51
EN
Description
Adjustable parameters
Presetting
Automatic
Start Delay
[Off], [On] = <hh>H <mm>M <ss>S
Adjustment: Hours, Minutes, Seconds
<00>H <00>M <00>S to <12>H <59>M <59>S
If Off, automatic restart is disabled on
the selected load segment and turns
on only when commanded manually by
on/off select button or via the display
(Control => Load Segments)
Load Segment
<1> 1s,
Load Segment
<2> 2s
Automatic
on Battery
Shutdown
[Off], [On] = <hh>H <mm>M <ss>S
Adjustment: Hours, Minutes, Seconds
<00>H <00>M <00>S to <12>H <59>M <59>S
Load Segment
<1> Off,
Load Segment
<2> Off
To control the load segments with power management software, see
your power management software manual for details. Refer to the
software “CompuWatch” (included on CD) or www.aegpartnernet.com
for latest information.
To control the load segments through the display:
1. Press “ESC” button to activate the menu options, and then select
CONTROL and LOAD SEGMENTS.
2. Set the desired load segment ON or OFF, and ENTER to confirm.
3. Set the other load segment if applicable.
To set the restart and shutdown delay times for each load segment:
1. Press “ESC” button to activate the menu options and then select
SETTINGS, and AUTOMATIC START DELAY.
2. Set the restart delay for one load segment, and ENTER to confirm.
3. Set the other load segment if applicable.
4. Select AUTOMATIC ON BATTERY SHUTDOWN.
5. Set the shutdown delay for one load segment, and ENTER to
confirm.
6. Set the other load segment if applicable.
i
Load segment On/Off commands issued through the
Control menu overrules the settings for load segments.