54
[enabled], [disabled]
“enabled” means UPS will have
bypass output when utility power on.
“disabled” means UPS will not have
bypass output when power on but
could get bypass output when UPS is
fault or overload.
[enabled], [disabled]
“enabled” means the UPS can be
started without installed battery system.
The number after “Total events” shows
how many events are currently stored
in the log.
Press the “ENTER” button for one
second to reset the event count to zero
and clear the log.
[-5], [-4], …[-1], [0], [+1], …[+4], [+5]
The LCD Contrast is adjustable and
the valid range is from -5 to +5.
[no], [yes]
Setting only available in UPS stand-by
mode.
Restoring the factory settings:
Returns all user-configurable
EEPROM settings to default
factory settings
Resets all pending on/off
commands
Clears the Event Log and resets
all time stamps
Resets the battery test status
Initiates the Self Diagnostics test
The “Restore Factory Settings“ process is completed after
the UPS was switched off completely. Wait until the fans
stopped to allow the UPS internal EEPROM overwriting.