54
−
Use tools with insulated handles.
−
Wear rubber gloves and boots.
−
Do not lay tools or metal parts on top of batteries.
−
Disconnect charging source prior to connecting or disconnecting
battery terminals.
−
Determine if battery is inadvertently grounded. If inadvertently
grounded, re-move source from ground. Contact with any part of
a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if such grounds are removed
during installation and maintenance.
−
Failed batteries can reach temperatures that exceed the burn
thresholds for touchable surfaces.
−
Product safety
These operating instructions comply with the current technical.
The UPS connection instructions and operation described in the
manual must be followed in the indicated order.
UPS enclosure IP rating IP20.
CAUTION - To reduce the risk of fire, the unit connects only to a
circuit provided with branch circuit overcurrent protection for:
20A rating, for Tower 3ks models, trip curve C .
The upstream circuit breaker for Normal AC/Bypass AC must be
easily accessible.
for PERMANENTLY CONNECTED EQUIPMENT, a readily
accessible disconnect device shall be incorporated external to the
equipment.
for PLUGGABLE EQUIPMENT, the socket-outlet shall be installed
near the equipment and shall be easily accessible.
Check that the indications on the rating plate correspond to your AC
powered system and to the actual electrical consumption of all the
equipment to be connected to the system.
Never install the system near liquids or in an excessively damp
environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in
a dry place.
The admissible storage temperature range is -25°C to +55°C without
batteries, 0°C to +40°C with batteries, suggest to storage the battery
below 25°C.