4.4 User settings
Password
Can be changed by user 4732
Change language
English, Italiano, Français, Deutsch,
Español, Русский, Polski,
简体中文
English
User password [enabled, ****], [disabled] enabled
Audible alarms [enabled], [disabled] enabled
Output voltage [200V], [208V], [220V], [230V], [240V] [230V]
Output frequency [autosensing], [converter 50Hz, 60Hz] autosensing
High efficiency mode [disabled], [enabled] disabled
Auto bypass [disabled], [enabled] disabled
Start/Auto
restart/Start from
bypass
[disabled], [enabled]
Cold start/Auto
restart: enabled
Start from bypass:
disabled
Site wiring fault [enabled], [disabled] disabled
Overload pre-alarm [10%~100%] 100%
External battery
[Auto detection],
[Manual EBP: 0~6],
Auto detection
Charger current
[2A], [4A], [6A], [8A] for long backup
model
4A
Dry in signal
[Disabled], [Remote on], [Remote off],
[Forced bypass]
disabled
Dry out signal
[load powered], [on bat], [Low bat], [bat
open], [bypass], [ups ok]
bypass