84
8.2 UPS Specifications
Model name PROTECT D LCD+
Rating 1KVA 1.5KVA 2KVA 2KVA “S” 3KVA 3KVA”S”
Power
rating
VA/Watt
1000VA/
1000W
1500VA/
1500W
2000VA/2000W 3000VA/3000W
Efficienc
y
Line
mode
89% 93%
ECO
mode
96% 97%
Input
perform
ance
Voltage
range
160-300V 100% load, 110-160V derating to 50% load linearly
Rated
frequenc
y
50Hz/60Hz
Frequenc
y range
40Hz-70Hz (45Hz-55Hz, 54Hz-66Hz @ load>60%)
PF >0.99
THDI <5%
Input
connecti
on
Socket 1x IEC C14 1x IEC C20
Output
perform
ance
Rated
voltage
200/208/220/230/240 VAC (derating 10% at 208V, derating 20% at
200V)
Rated
frequenc
y
50Hz/60Hz
Maximu
m PF
PF = 1
Voltage
accuracy
±1%
THDv <1% linear load; <5% nonlinear load
Transfer
time
0ms@line <-> battery; 4ms @ line <-> bypass; 10ms @ ECO
<->Inverter
Crest
Ratio
Max 3:1
Overload
100%<load≤105% continuous.
105%< load ≤125% for 5 minutes
125<load≤150% for 30 seconds.
>150% for 500ms.