EasyManua.ls Logo

AEMC 3640 - Soil Resistivity Measurement Procedure (4-Point)

AEMC 3640
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
34
Digital Ground Resistance Tester Model 3640 and 4610
4.10 Soil Resistivity Measurement Procedure (4-Point)
Assumingthattheobjectiveislowresistivity,preferenceshouldbegiven
toanareacontainingmoistloamasopposedtoadrysandyarea.Consid-
erationmustalsobegiventothedepthatwhichresistivityisrequired.
• DisconnecttheshortingstripfromtheXandXvterminals.
• Arrangetheelectrodesinastraightline.Besurethatdistancesbetween
electrodesareidentical:e.g. 3 metersbetween eachelectrode (See
Figure20).
• Thedistancebetweenpolesisproportionaltotheaveragedepthofthe
soilsampleyouwishtomake.
• Theelectrodesshouldbeplacedatadepthofapproximately6inches
(0.15meters),sothatthedepthisapproximately1/20thofthedistance
betweenelectrodes.
• UseleadstoconnecttheX,Xv,Y,andZelectrodestotherespective
terminalsontheDigitalGroundResistanceTester.
• Pressthe“Measure”button.
• Readtheresistancelevel(R)indicatedonthedisplay.
• In the event of difculties in performing measurements, consult the
previousinstructionsconcerninggroundresistancemeasurements.
• Applythefollowingformulainordertodetermineresistivity(ρ):
ρ
= 2πxRxA
A=distancebetweenelectrodesinmeters
ρ
= resistivity in meters
R=ohmsreadingobtainedonModel4610
Example 1: For measurement performed in soil with a high limestone content, the
reading is R = 225, with A = 3 meters.
ρ
= 2πx225x3m
ρ
= 4239m
Example 2: After inspection, the area to be investigated has been narrowed down
to a plot of ground approximately 75 square feet (22.5m
2
). Assume that you need to
determine the resistivity at a depth of 15 feet (457cm). The distance “A between
the electrodes must then be equivalent to the depth at which average resistivity is
to be determined (15 ft, or 450cm). Using the more simplified Wenner formula (
ρ
= 2πAR), the electrode depth must then be 1/20th of the electrode spacing or 8"
(22.5cm). If the electrode depth is greater than 1/20th of the electrode spacing, the
following formula must be used:

Table of Contents

Related product manuals