7
Clamp-On Harmonic Probe Model
AC VOLTAGE (TRMS)
Input Range: 0.05 to 600 Vrms
± 0.05 to ±1500 V Peak
Basic Accuracy: 0.05 to 59.99 V: 1% R ±10 cts
60 to 1500 V peak: 1%R ±2 cts
Input Impedance: 1 M
Frequency Range: 0.5 Hz to 5 kHz
DC CURRENT
Input Range: ± 0.03 to ± 1500 A DC
± 0.05 to ± 1500 A Peak
Basic Accuracy: ± 0.3 to ± 59.99 A: 2% R ± 20 cts
± 60 to ± 1500 A: 2% R ± 2 cts
DC VOLTAGE
Input Range: ± 0.05 to ±600 V
Basic Accuracy: 0.05 to 59.99 V: 1% R ±10 cts
60 to 1500 V peak: 1% R ±2 cts
Input Impedance: 1 M
TOTAL HARMONIC DISTORTION (%THD)
Range: 0.2% to 1000%
Resolution: 0.1%
Basic Accuracy: 0.2% to 600% THD: 5%R ± 2cts
Frequency Range: Fundamental 40 Hz to 70 Hz
Display: Digital: %THD and True RMS (A or V)
Bar graph: True RMS (A or V)
DISTORTION FACTOR (%DF)
Range: 0.2% to 100%
Resolution: 0.1%
Minimum Input: 10 V or 10 A
Basic Accuracy: 5% R ± 2 cts
Frequency Range: Fundamental 40 Hz to 70 Hz
Display: Digital: %DF and True RMS (A or V)
Bar graph: True RMS (A or V)