205
POWER CLAMP-ON METER
User Manual
ENGLISH

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the AEMC 205 and is the answer not in the manual?

Overview

The AEMC Model 205 is a professional electrical measuring instrument designed for a wide range of electrical measurements.

Function Description:

The Model 205 combines multiple functions, including:

  • Current measurement (AC, DC, AC+DC)
  • Measurement of InRush current / overcurrent (True InRush®)
  • Voltage measurement (AC, DC, AC+DC)
  • Frequency measurement (Hz)
  • Measurement of harmonic distortion (THD, THDf, THDr)
  • Continuity test with buzzer
  • Resistance measurement (Ω)
  • Diode test
  • Power measurements (W, VA, var, and PF)
  • Phase order indication

Important Technical Specifications:

General:

  • Safety Standards: IEC-61010-1, IEC-61010-2-30, and IEC-61010-2-32 for voltages of 1000V in category III or 600V CAT IV.
  • Altitude: Less than 2000m, indoors.
  • Pollution Degree: Not exceeding 2.
  • Power Supply: 1x9V LF22 battery.
  • Battery Life: >120 hours (without backlighting).
  • Auto Power Off: After 10 minutes of inactivity.
  • Electromagnetic Compatibility: Compliant with EN-61326-1 (residential environment).
  • Mechanical Strength: Free fall: 2m (IEC-68-2-32).
  • Housing Protection: IP40 (IEC-60529).
  • Housing: Rigid polycarbonate shell with over-molded elastomer covering; UL94 V1.
  • Jaws: Polycarbonate, 1.3" (34mm) opening/clamping diameter.
  • Screen: LCD display unit with blue backlighting, 1.1 x 1.7" (28 x 43.5mm).
  • Dimensions: 8.7 x 3.0 x 1.65" (222 x 78 x 42mm).
  • Weight: 0.86 lbs (340g) with batteries.

Reference Conditions:

  • Temperature: 23°C ±2°C
  • Relative Humidity: 45% to 75%
  • Supply Voltage: 9.0V ±0.5V
  • Frequency Range: 45 to 65Hz
  • Sine Wave: Pure
  • Peak Factor: √2
  • Conductor Position: Centered in the clamp.
  • Adjacent Conductors/Magnetic/Electric Field: None.

Environmental Conditions:

  • Operating Temperature: -4° to +131°F (-20° to +55°C).
  • Storage Temperature: -40° to +158°F (-40° to +70°C).
  • Relative Humidity (RH): ≤90% up to 131°F (55°C) operating, ≤90% up to 158°F (70°C) storage.

Measurement Ranges & Accuracy (under reference conditions):

DC Voltage:

  • Ranges: 0.00 to 59.99V, 60.0 to 599.9V, 600V to 1000V.
  • Accuracy: ±(1% R + 10cts) for 0.00-5.99V, ±(1% R + 3cts) for 6.00-1000V.
  • Resolution: 0.01V, 0.1V, 1V.
  • Input Impedance: 10MΩ.
  • Note: Displays "+OL" above +2000V and "-OL" below -2000V in REL mode. Repetitive beep above 1000V.

AC Voltage:

  • Ranges: 0.15 to 59.99V, 60.0 to 599.9V, 600V to 1000V RMS (1400V peak).
  • Accuracy: ±(1% R + 10cts) for 0.15-5.99V, ±(1% R + 3cts) for 6.00-1000V.
  • Resolution: 0.01V, 0.1V, 1V.
  • Input Impedance: 10MΩ.
  • Note: Displays "OL" above 1000V (1400V in PEAK mode). Bandwidth in AC = 3kHz.

AC+DC Voltage:

  • Ranges: 0.15 to 59.99V, 60.0 to 599.9V, 600V to 1000V RMS (1400V peak).
  • Accuracy: ±(1% R + 10cts) for 0.15-5.99V, ±(1% R + 3cts) for 6.00-1000V.
  • Resolution: 0.01V, 0.1V, 1V.
  • Input Impedance: 10MΩ.
  • Note: Displays "OL" above 1000V (1400V in PEAK mode). Bandwidth in AC = 3kHz.

DC Current:

  • Ranges: 0.00 to 59.99A, 60.0 to 599.9A, 600A to 900A.
  • Accuracy (zero corrected): ±(1% R + 10cts) for 0.00-59.99A, ±(1% R + 3cts) for 60.0-900A.
  • Resolution: 0.01A, 0.1A, 1A.
  • Note: Displays "+OL" above 1800A and "-OL" below -1800A in REL mode. Residual current at zero can be corrected by "DC zero" function.

AC Current:

  • Ranges: 0.15 to 59.99A, 60.0 to 599.9A, 600A.
  • Accuracy: ±(1% R + 10cts) for 0.15-59.99A, ±(1% R + 3cts) for 60.0-600A.
  • Resolution: 0.01A, 0.1A, 1A.
  • Note: Displays "OL" above 900A (in PEAK mode). Bandwidth in AC = 3kHz. Values between 0 and 0.15A show "----".

AC+DC Intensity:

  • Ranges: 0.15 to 59.99A, 60.0 to 599.9A, AC: 600A, DC or PEAK: 600A to 900A.
  • Accuracy (zero corrected): ±(1% R + 10cts) for 0.15-59.99A, ±(1% R + 3cts) for 60.0-900A.
  • Resolution: 0.01A, 0.1A, 1A.
  • Note: Displays "+OL" above +1800A and "-OL" below -1800A in REL mode (DC). Displays "+OL" above 1500A in PEAK mode (AC/AC+DC). Bandwidth in AC = 3kHz.

True InRush® Measurement:

  • Ranges: 6 to 600AAC, 6 to 900ADC.
  • Accuracy: ±(5% R + 5cts).
  • Resolution: 1A.
  • Note: Triggering threshold is 10A if initial current is zero.

Continuity Measurement:

  • Range: 0.0 to 599.9Ω.
  • Open-circuit Voltage: ≤ 3.6V.
  • Measurement Current: 550μA.
  • Accuracy: ±(1% R + 5cts).
  • Buzzer Triggering Threshold: Adjustable from 1 to 599Ω (40Ω default).

Resistance Measurement:

  • Ranges: 0.0 to 599.9Ω, 600 to 5999Ω, 6 to 59.99KΩ.
  • Accuracy: ±(1% R + 5cts).
  • Resolution: 0.1Ω, 1Ω, 10Ω.
  • Open-circuit Voltage: ≤ 3.6V.
  • Measurement Current: 550μA, 100μA, 10μA.
  • Note: Displays "OL" above maximum display value.

Diode Test:

  • Range: 0.000 to 3.199VDC.
  • Accuracy: ±(1% R + 10cts).
  • Resolution: 0.001V.
  • Measurement Current: 0.55mA.
  • Indication: "OL" for measured voltage >3.199V (junction reversed or open-circuit).

Active DC Power Measurements:

  • Ranges: 0 to 5.999W, 6.00 to 59.99kW, 60.0 to 599.9kW, 600 to 900kW.
  • Accuracy: ±(2% R + 10cts) for 0-5.999W, ±(2% R + 3cts) for 6.00-900kW.
  • Resolution: 1W, 10W, 100W, 1000W.
  • Note: Displays O.L or ±O.L above ±1800kW in REL mode. Instability linked to current measurement (approx. 0.1A).

Active AC Power Measurements:

  • Ranges: 5 to 5999W, 6.00 to 59.99kW, 60.0 to 599.9kW, 600kW.
  • Accuracy: ±(2% R + 10cts) for 5-5999W, ±(2% R + 3cts) for 6.00-600kW.
  • Resolution: 1W, 10W, 100W, 1000W.
  • Note: Bandwidth in AC (voltage/current) = 3kHz. Power < 5W or V < 0.15V or I < 0.15A displays "----".

Active AC+DC Power Measurements:

  • Ranges: 5 to 5999W, 6.00 to 59.99kW, 60.0 to 599.9kW, 600 to 900kW.
  • Accuracy: ±(2% R + 10cts) for 5-5999W, ±(2% R + 3cts) for 6.00-900kW.
  • Resolution: 1W, 10W, 100W, 1000W.
  • Note: Bandwidth in AC (voltage/current) = 3kHz.

Apparent AC Power:

  • Ranges: 5 to 5999VA, 6.00 to 59.99kVA, 60.0 to 599.9kVA, 600kVA.
  • Accuracy: ±(2% R + 10cts) for 5-5999VA, ±(2% R + 3cts) for 6.00-600kVA.
  • Resolution: 1VA, 10VA, 100VA, 1000VA.
  • Note: Bandwidth in AC (voltage/current) = 3kHz.

Apparent AC+DC Power:

  • Ranges: 5 to 5999VA, 6.00 to 59.99kVA, 60.0 to 599.9kVA, 600 to 900kVA.
  • Accuracy: ±(2% R + 10cts) for 5-5999VA, ±(2% R + 3cts) for 6.00-900kVA.
  • Resolution: 1VA, 10VA, 100VA, 1000VA.
  • Note: Displays OL above 900kVA in single-phase (1000V x 900A). Bandwidth in AC (voltage/current) = 3kHz.

Reactive AC Power:

  • Ranges: 5 to 5999 var, 6.00 to 59.99 kvar, 60.0 to 599.9 kvar, 600 kvar.
  • Accuracy: ±(2% R + 10cts) for 5-5999 var, ±(2% R + 3cts) for 6.00-600 kvar.
  • Resolution: 1 var, 10 var, 100 var, 1 kvar.
  • Note: Bandwidth in AC (voltage/current) = 3kHz.

Reactive AC+DC Power:

  • Ranges: 5 to 5999 var, 6.00 to 59.99 kvar, 60.0 to 599.9 kvar, 600 to 900 kvar.
  • Accuracy: ±(2% R + 10cts) for 5-5999 var, ±(2% R + 3cts) for 6.00-900 kvar.
  • Resolution: 1 var, 10 var, 100 var, 1 kvar.
  • Note: Displays OL above 900 kvar in single-phase (1000V x 900A). Bandwidth in AC (voltage/current) = 3kHz.

Power Factor:

  • Range: -1.00 to +1.00.
  • Accuracy: ±(3% R + 3cts) for 0 to 50% of range, ±(2% R + 3cts) for 50 to 100% of range.
  • Resolution: 0.01.
  • Note: Displays "----" if calculation is impossible (OL, forced to zero).

Frequency Measurements:

  • Voltage Range: 5.0 to 599.9Hz, 600 to 5999Hz, 6.00 to 19.99kHz.
  • Accuracy: ±(0.4% R + 1ct).
  • Resolution: 0.1Hz, 1Hz, 10Hz.
  • Current Range: 5.0 to 599.9Hz, 600 to 2999 Hz.
  • Accuracy: ±(0.4% R + 1ct).
  • Resolution: 0.1Hz, 1Hz.
  • Note: Displays "----" if input signal is too low (V<3V or I<3A) or frequency < 5Hz.

Specifications in THDr:

  • Range: 0.0 to 100%.
  • Accuracy: ±(5% R ±2cts) in voltage, ±(5% R ±5cts) in current.
  • Resolution: 0.1%.

Specifications in THDf:

  • Range: 0.0 to 1000%.
  • Accuracy: ±(5% R ±2cts) in voltage, ±(5% R ±5cts) in current.
  • Resolution: 0.1%.
  • Note: Displays "----" if input signal is too low (V<5V or I<6A) or frequency < 5Hz.

Indication of Phase Order:

  • Frequency Range: 47 to 400Hz.
  • Acceptable Voltage Range: 50 to 1000V.
  • Acquisition Duration Period: ≤500ms.
  • Validity Duration Period: Approx. 10s at 50Hz, 2s at 400Hz.
  • Acceptable Phase Unbalance: ±10.
  • Acceptable Amplitude Unbalance: 20%.
  • Acceptable Level of Harmonics in Voltage: 10%.

Usage Features:

  • Rotary Switch: Six positions for selecting measurement functions (OFF, V, Ω, A, W, 1-2-3Φ).
  • Function Buttons:
    • HOLD: Stores the last value on the display, performs DC zero correction, lead resistance compensation.
    • Yellow Button (Second Function): Selects AC/DC/AC+DC measurement types, configures default values, cycles through continuity/resistance/diode test, resets phase order indication, displays total 3-phase power.
    • Backlight Button: Enables/disables display backlighting (auto-disabled after 2 minutes).
    • MAX/MIN/PEAK Button: Activates detection of MAX, MIN, PEAK+ (maximum instantaneous peak), and PEAK- (minimum instantaneous peak) values. Disables Auto Power Off.
    • Hz Button: Performs frequency measurements, selects harmonic distortion measurements (THDf, THDr), displays powers (W, VA, var, PF). Not functional in DC mode.
    • AREL Button: Stores a reference value, displays differential and relative values. Not functional in phase rotation mode.
  • Terminals: COM (black) and + (red) input terminals for voltage, resistance, continuity, and diode measurements.
  • Jaws: Opened by a trigger on the meter body for current measurements. Arrow on jaws indicates presumed direction of current flow. Optimal results when conductor is centered.
  • Configuration: Default parameters can be reset by holding the yellow button while turning the switch to A from OFF.
  • Auto Power Off: Enabled by default (10 minutes of inactivity). Can be disabled for certain modes (e.g., MAX/MIN/PEAK).
  • InRush Measurement: Initiated by a long press of the MAX/MIN/PEAK button in current mode. Measures starting or overcurrent.

Maintenance Features:

  • Battery Replacement: Indicated by a low battery symbol on the display. Requires unscrewing the battery compartment cover, replacing the 9V LF22 battery, and re-securing the cover. Test leads must be disconnected.
  • Cleaning: Disconnect all connections, set the switch to OFF. Use a soft cloth moistened with soapy water, rinse with a damp cloth, and dry thoroughly.
  • Calibration: Recommended at one-year intervals by the factory Service Center or as required by internal procedures. An NIST traceable certificate can be requested.
  • Repair: Requires obtaining a Customer Service Authorization Number (CSA#) from the Service Department before returning the instrument.
  • Safety Precautions: Emphasizes reading the manual, not using in explosive atmospheres, observing voltage/current limits, not using if damaged, checking insulation, using rated leads, not modifying the instrument, and performing configuration when disconnected from dangerous voltages.