Setting Description
0 report power, energy absolute value
1 report positive/negative power, report the algebraic sum energy
2
report positive/negative power, only report energy
positive part (consuming electricity)
3
report positive/negative power, only report energy
negative part (generating electricity)
Parameter 3: Selective reporting
Enable selective reporting only when power change reaches a certain threshold or percentage set in 4-11 below.
This is used to reduce network traffic. Size: 1 Byte, Default Value: 1
Setting Description
0 disable
1 enable
Parameter 4: Threshold change in wattage
Threshold change in wattage to induce a automatic report (Whole HEM).
Size: 2 Byte, Default Value: 50
Setting Description
0 – 60000 Watt
Parameter 5: Threshold change in wattage (Clamp 1)
Threshold change in wattage to induce a automatic report
Size: 2 Byte, Default Value: 50
Setting Description
0 – 100 Valid value