Cooling capacity correction factors 0,99 1 1,02 1,03
Input capacity correction factors 0,99 1 1,01 1,02
0,00005 0,0001 0,0002
Cooling capacity correction factors 1 0,98 094
Input capacity correction factors 1 0,98 0,95
8.7. FOR ΔT DIFFERENT FROM THE
RATED VALUE
The performances given by the techni-
cal data refer to t 5°C.
Use table to obtain the corrective fac-
tors of the cooling capacity and input
power different than t 5°C.
8.8. FOULING FACTORS
The performance levels indicated in the
technical data refer to conditions with
clean tubes, with a fouling factor = 1.
For other fouling factor values, multiply
the data of performance table by the
coefficients given.
8.8.1. Δt different from the rated value
8.8.2. Fouling factors
[k*m
2
]/[w]