38 22.11 5806712_07
POWER SUPPLY 230V
Version
Integrated
hydronic kit user
side
Integrated
hydronic kit,
recovery side
0800 0900 1000 1250 1400 1500 1650 1800
Peak current (LRA)
A 00 00 A 578 751 781 935 956 1011 1046 1115
A 00 R1/R2 A 589 769 799 953 981 1036 1071 1140
A 00 R3/R4 A 591 776 806 960 991 1046 1081 1150
A P1/P2 00 A 589 762 792 953 974 1029 1064 1133
A P1/P2 R1/R2 A 600 780 810 971 998 1053 1088 1157
A P1/P2 R3/R4 A 602 786 816 977 1009 1064 1099 1168
A P3/P4 00 A 591 764 794 960 981 1036 1071 1140
A P3/P4 R1/R2 A 602 782 812 977 1005 1060 1095 1164
A P3/P4 R3/R4 A 605 789 819 984 1016 1071 1106 1175
Minimum circuit
amperage (MCA)
A 00 00 A 282 323 374 422 477 526 562 593
A 00 R1/R2 A 293 341 392 440 502 551 587 618
A 00 R3/R4 A 295 348 399 447 512 561 597 628
A P1/P2 00 A 293 334 385 440 495 544 580 611
A P1/P2 R1/R2 A 304 352 403 458 519 568 604 635
A P1/P2 R3/R4 A 306 358 409 464 530 579 615 646
A P3/P4 00 A 295 336 387 447 502 551 587 618
A P3/P4 R1/R2 A 306 354 405 464 526 575 611 642
A P3/P4 R3/R4 A 309 361 412 471 537 586 622 653
Maximum over
-
current permitted
by the protection
device (MOP)
A 00 00 A 338 397 448 508 587 635 672 678
A 00 R1/R2 A 349 415 466 526 612 660 697 703
A 00 R3/R4 A 351 422 473 533 622 670 707 713
A P1/P2 00 A 349 408 459 526 605 653 690 696
A P1/P2 R1/R2 A 360 426 477 544 629 677 714 720
A P1/P2 R3/R4 A 362 432 483 550 640 688 725 731
A P3/P4 00 A 351 410 461 533 612 660 697 703
A P3/P4 R1/R2 A 362 428 479 550 636 684 721 727
A P3/P4 R3/R4 A 365 435 486 557 647 695 732 738
POWER SUPPLY 460V
Version
Integrated
hydronic kit user
side
Integrated
hydronic kit,
recovery side
0800 0900 1000 1250 1400 1500 1650 1800
Peak current (LRA)
A 00 00 A 293 343 358 430 480 505 521 511
A 00 R1/R2 A 299 352 367 439 492 517 533 523
A 00 R3/R4 A 300 355 370 442 497 522 538 528
A P1/P2 00 A 299 349 364 439 489 514 530 520
A P1/P2 R1/R2 A 304 357 372 448 501 526 542 532
A P1/P2 R3/R4 A 305 361 376 451 506 531 547 537
A P3/P4 00 A 300 350 365 442 492 517 533 523
A P3/P4 R1/R2 A 305 359 374 451 504 529 545 535
A P3/P4 R3/R4 A 306 362 377 454 510 535 551 541
Minimum circuit
amperage (MCA)
A 00 00 A 139 148 165 214 242 267 284 298
A 00 R1/R2 A 145 157 174 223 254 279 296 310
A 00 R3/R4 A 146 160 177 226 259 284 301 315
A P1/P2 00 A 145 154 171 223 251 276 293 307
A P1/P2 R1/R2 A 150 162 179 232 263 288 305 319
A P1/P2 R3/R4 A 151 166 183 235 268 293 310 324
A P3/P4 00 A 146 155 172 226 254 279 296 310
A P3/P4 R1/R2 A 151 164 181 235 266 291 308 322
A P3/P4 R3/R4 A 152 167 184 238 272 297 314 328
Maximum over
-
current permitted
by the protection
device (MOP)
A 00 00 A 165 178 195 256 296 322 338 339
A 00 R1/R2 A 171 187 204 265 308 334 350 351
A 00 R3/R4 A 172 190 207 268 313 339 355 356
A P1/P2 00 A 171 184 201 265 305 331 347 348
A P1/P2 R1/R2 A 176 192 209 274 317 343 359 360
A P1/P2 R3/R4 A 177 196 213 277 322 348 364 365
A P3/P4 00 A 172 185 202 268 308 334 350 351
A P3/P4 R1/R2 A 177 194 211 277 320 346 362 363
A P3/P4 R3/R4 A 178 197 214 280 326 352 368 369