16. CAPACITY CONTROL
Capacity step control (cold)
* Cooling capacity % Levels of power
Versions 1° 2° 3° 4°
NXW0500 39 55 100 -
NXW0550 36 70 100 -
NXW0600 28 53 78 100
NXW0650 28 53 78 100
NXW0700 28 53 78 100
NXW0750 28 53 78 100
NXW0800 28 53 78 100
NXW0900 28 53 78 100
NXW1000 28 53 78 100
NXW1250 28 53 78 100
NXW1400 28 53 78 100
* Input power % Levels of power
Versions 1° 2° 3° 4°
NXW0500 33 49 100 -
NXW0550 30 64 100 -
NXW0600 22 47 72 100
NXW0650 22 47 72 100
NXW0700 22 47 72 100
NXW0750 22 47 72 100
NXW0800 22 47 72 100
NXW0900 22 47 72 100
NXW1000 22 47 72 100
NXW1250 22 47 72 100
NXW1400 22 47 72 100
Performance values refer to the following conditions:
* Evaporator inlet water temperature = 7°C
condenser inlet water temperature = 35°C