KEY
Sec. A: Power supply
Sec. B: Controls and safety connection
Earth
IL: Main switch
49
INXWPY. 1004. 4438805_00
Model
MAX
RECOMMENDED
LENGTH
SECT. A
(400V-3)
SECT.B
EARTH
(400V-3)
IL
(400V-3)
U.M. U.M. U.M. U.M. U.M.
MT mm
2
mm
2
mm
2
A
NXW 0500
50
16
1.5
16 100
NXW 0550 25 16 100
NXW 0600 25 16 125
NXW 0650 35 16 125
NXW 0700 50 25 160
NXW 0750 50 25 160
NXW 0800 70 35 200
NXW 0900 70 35 200
NXW 1000 95 50 250
NXW 1250 95 50 250
NXW 1400 95 50 250
ELECTRICAL DATA VERSION WITH PUMPING GROUP
(ALL VERSIONS)

Table of Contents