Introduction
06
3.2.5 EPS
3.2.6 Timed charge and discharge
When the grid is suddenly off or abnormal, inverter will change to off grid status
automatically. Energy from PV system and battery will supply the local load.
There are 4 types of timed charge and discharge control, each of which can be
set for 3 time periods respectively. It operates according to these four types
within the set time period, and resumes operation in the setting mode of
3.2.1~3.2.4 after the time expires.
3.2.6.1 AC Charge
During the set time period, the battery is charged with the set power. When the
PV power is not enough, the power is drawn from the grid until the set SOC is
reached, and the timing charging function is stopped.
3.2.6.2 Force Charge
During the set time period, the battery is charged with the set power, and the
power is only drawn from the PV, not from the grid, and the timing charging
function is stopped after the set SOC.
3.2.6.3 Force Discharge
During the set time period, discharge the battery with the set power until the set
SOC stops the timed discharge function.
3.2.6.4 Forbid discharge
During the set time period, the PV power will give priority to the charging, not
the load1.