Installation
21
10±0.5mm
Note:
The wiring terminals should be wrapped with insulation tape,
otherwise it will cause a short circuit and damage the inverter.
Cable suggestion:
6-8kW Cross-section (Copper) 4-6mm² / 10AWG
9-10kW Cross-section (Copper) 6-10mm² / 8AWG
After the terminals are crimpped, wrap the joint position with insulation tape.
Step 1
Single-Phase (HNS6000TL / HNS7000TL / HNS8000TL /
HNS9000TL / HNS10000TL):
Step 2
HNS6000TL / HNS7000TL / HNS8000TL
Unscrew the row of screws, insert the wire harness into the
L, N, PE caps one by one, and tighten the screws.
L=Live line
N=Neutral line
L
N
DRM
WIFI