Condensate Pumps
7KH6PDUW&RROFRQGHQVDWHSXPSVKDOOEHHLWKHUKRWZDWHUIXOOIXQFWLRQXQLWVZKHQDKXPLGL¿HULV¿WWHGRUFROGZDWHU
type (Cooling only).
Performance
The following graphs illustrate the TOTAL static (head) pressure available. The system horizontal pipe losses and
vertical lift should be factored in when calculating the condensate pump performance.
Cold Water (Cooling only units)
IMPORTANT
The discharge line from the pump should rise no more than 6 metres vertically and no more than 8 metres in total
length before being interrupted with a swan neck air break and tundish.
Condensate Drain Tray Monitoring
$ÀRDWOHYHOVZLWFKVKDOOEHLQFRUSRUDWHGLQWRWKHXQLWGUDLQWUD\IRULQGLFDWLRQRIDKLJKZDWHUDODUP
Hot Water (Full function units)
The cold water condensate
pump has 10mm quarter turn
SODVWLF³EDUEHG´FRQQHFWLRQ
The hot water condensate
SXPSXVHVPP´FRSSHU
tube when connecting to the
discharge stub of the pump.
2
4
6
8
10
12
0
5.0 9.07.0 13.0 15.011.0
Head (m) Head (m)
0
1
2
3
4
5
6
0.0 0.5 1.0 1.5 2.0 2.5 3.0
Flow Rate (l/min)
Flow Rate (l/min)
SmartCool™ 16 - 60
Precision Air Conditioning
28