19
1.
4.
(1) Additional refrigerant charging amount= prolonged length of liquid pipe × additional
capacity
24000Btu/h
The calculation method of additional refrigerant oil and refrigerant charging amount
after prolonging connection pipe
After the length of connection pipe is prolonged for 10m at the basis of standard
length, you should add 5ml of refrigerant oil for each additional 5m of connection
pipe.
The calculation method of additional refrigerant charging amount (on the basis
of liquid pipe):
(7032W)
9000Btu/h
(2637W)
12000Btu/h
(3516W)
18000Btu/h
(5274W)
Max. length of
connection pipe
25
Unit: m
15
20
25
2.
3.
Standard length of connection pipe
5m7.5m8m
Configuration of connection pipe
Min. length of connection pipe
For the unit with standard connection pipe of 5m, there is no limitation for the
min. length of connection pipe. For the unit with standard connection pipe of
7.5m and 8m, the min. length of connection pipe is 3m.
Max. length of connection pipe
Sheet 1 Max. length of connection pipe
refrigerant charging amount per meter
(2)
Basing on the length of standard pip
e, add refrigerant according to the
requirement as shown in the table. The additional refrigerant charging amount
per meter is different according to the diameter of liquid pipe. See Sheet 2.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Airwell AW-YHDL018-H91 and is the answer not in the manual?

Airwell AW-YHDL018-H91 Specifications

General IconGeneral
BrandAirwell
ModelAW-YHDL018-H91
CategoryAir Conditioner
LanguageEnglish

Related product manuals