RATING CONDITIONS
Service Manual YBZE DCI 1-A.1 GB 3-1
3. RATING CONDITIONS
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
Cooling:
Indoor: 27
o
C DB 19
o
C WB
Outdoor: 35
o
C DB
Heating:
Indoor: 20
o
C DB
Outdoor: 7
o
C DB 6
o
C WB
Operating Limits
R410A
Indoor
Outdoor
Cooling
Upper limit
32
o
C DB 23
o
C WB
48
o
C DB
Lower limit
21
o
C DB 15
o
C WB
-15
o
C DB
Heating
Upper limit
27
o
C DB
24
o
C DB 18
o
C WB
Lower limit
10
o
C DB
-15
o
C DB RH80%
Voltage
1-PH 50Hz 195 265 V