25
SYSTEM PARAMETERS
System address. Use this parameter to define the system number in your installation using this parameter. The
Supermaster option (available in installations with production control board, AZX6CCP) allows you to impose the
operation mode of the system to the rest of the systems connected to the AZX6CCP in a semi-forced way:
Temperature range. Use this parameter to select the highest temperature in heating mode (19-30 ºC, by default 30ºC)
and the lowest temperature in cooling mode (18-26 ºC, by default 18ºC). It is also possible to disable some of the
modes.
Combined stage. Use this parameter to activate or deactivate the combined stage.
Hysteresis Configuration. Defines the temperature differential between the room temperature and the set-point
temperature required to start applying the Algorithm RadianT. This algorithm prevents overheating in underfloor air
conditioning installations. If your installation has radiators, set this value to 0ºC. (By default 2ºC)
Type of opening. Use this parameter to configure the type of opening of the damper output.
*Note: If you change this parameter, all the dampers of the installation will be affected. It is not recommended for RINT and
RIC intelligent grilles.
Relay settings. Use this parameter to change the operation logic of the CMV/Boiler of the system main control board.
(By default CMV)
Return temperature (only available for installations with AZX6SONDPROTEC). Defines the cut-off temperatures of the
system for both heating (32ºC, 34ºC and 36ºC) and cooling mode (6ºC, 8ºC and 10ºC) in order to protect the AC unit. It
is set by default in 34ºC in heating mode and 8ºC in cooling mode.
Q-Adapt (only for Think thermostats). Select the control algorithm that best fits your installation. These are the available
options:
- Maximum: The system operates at maximum speed, irrespective of the number of zones.
- Power: The speed of the system is higher than in standard mode to increase the flow.
- Standard: Mode by default. The system automatically regulates the speed based on the number of zones.
- Silence: The speed of the system is lower than in standard mode to reduce the noise.
- Minimum: The system operates at minimum speed, irrespective of the number of zones.
Radio channel. It activates/deactivates the wireless association module of the system.
Information (only for Think thermostats). It provides information about the zone, the system, the devices and the
Webserver.
Available operation modes:
Rest of the systems