14
A-MIP 210 V1.06
Specifications
Mechanical characteristics
• Weight
• X2A210-XX000:2,9 Kg.
• X2A210-XX100 (siren option): 3,1 Kg.
• X2A210-XX001 (heating option): 3 Kg.
• X2A210-XX101 (siren & heating option): 3,3 Kg.
• Composition:
• Door: Polycarbonate.
• Chassis: ABS.
• Square: ABS.
Electrical characteristics
• Power supply:
24 VDC 75 Watts, limited power source.
• Aivia operating temperatures:
Minimum: -20°C.
Maximum: 55°C.
• Temperature alerts:
Low temperature alert: defined by user. (5°C by
default).
High temperature alert: defined by user.(40°C by
default)
• Heating option:
(Reférences: X2A220-XX001 or X2A220-XX101)
Heating thresold : defined by user. (10°C by default).
Fan thresold: defined by user. (30°C by default).
• Current consumption:
• X2A210-XX000:
Minimum: 55mA.
Maximum: 200 mA.
Compliance
EN 55022:2006
EN 55024: 1998/ A1 : 2001/ A2 : 2003
EN 60950-1 : 2006
Dimensions en mm
• X2A210-XX100 (siren option):
Minimum: 55 mA.
Maximum: 500 mA.
Sound level: 90-105 dB / 1 meter.
• X2A210-XX001(heating option):
Minimum: 55 mA.
Maximum: 2000 mA.
• X2A210-XX101 (siren and heating option):
Minimum: 55 mA.
Maximum: 2400 mA.