9. FAULTS
9.1. With error code
If an error code appears on the screen, please contact your installer or maintenance company.
When an error occurs, it is possible to change mode or adjust the temperature setpoint. However, displaying the error takes
priority over the other displays.
If the fault relates to the heat pump, “SAFE” mode (back-up) is triggered automatically: the water is heated with the electrical
boost only. Some faults require the water heater to be shut down completely.
Code displayed
Message
displayed
Causes
Consequences on the water heater
operation
Er01
SENSOR <>
TANK
The two water
temperature sensors (on
the top and bottom of the
tank) are defective or not
connected.
Water not heating: stop heat pump and electrical boost.
Fan in operation (CMEV) for version
B200-FAN_T.FLOW HYGRO+ / B100-FAN_T.FLOW NANO
(with built-in fan).
Er02
SENSOR <>
T°BOT
Water temperature sensor
at tank bottom defective.
Stop the heat pump and heat the water with electrical boost
only (SAFE mode).
Fan in operation (CMEV) for version
B200-FAN_T.FLOW HYGRO+ / B100-FAN_T.FLOW NANO
(with built-in fan).
Er03
SENSOR <>
T°TOP
Water temperature sensor
at tank top defective.
Water heated with heat pump and electrical boost prohibited.
Fan in operation (CMEV) for version
B200-FAN_T.FLOW HYGRO+ / B100-FAN_T.FLOW NANO
(with built-in fan).
Er04
SENSOR <>
T°HP
Refrigerating line
temperature sensor at
compressor outlet (HP)
defective.
Stop the heat pump and heat the water with electrical boost
only (SAFE mode).
Fan in operation (CMEV) for version
B200-FAN_T.FLOW HYGRO+ / B100-FAN_T.FLOW NANO
(with built-in fan).
Er05
SENSOR <>
T°EVAP
Evaporator temperature
sensor defective.
Er06
SENSOR <>
T°AIR
Incoming air temperature
sensor (CMEV) defective.
Er07
FAN <>
ENGINE
Fan rotation speed
outside range.
Stop the heat pump and heat the water with electrical boost
only (SAFE mode).
Stop the fan (no CMEV) for version B200-FAN_T.FLOW
HYGRO+ / B100-FAN_T.FLOW NANO (with built-in fan).
Er08
SENSOR <>
PRESS <>
PCB
Electronic board pressure
sensor defective.
Water heated with heat pump and electrical boost.
Fan (CMEV) adjusted to fixed flow based on the set
configuration (number of exhaust grilles).
Er09
ANODE
Titanium anode board
alarm contact open: fault
on anode board.
Water not heating: stop heat pump and electrical boost.
Fan in operation (CMEV) for version
B200-FAN_T.FLOW HYGRO+ / B100-FAN_T.FLOW NANO
(with built-in fan).
Er10
COMM <>
COMP
Communication with
inverter module defective.
Stop the heat pump and heat the water with electrical boost
only (SAFE mode).
Fan in operation (CMEV) for version
B200-FAN_T.FLOW HYGRO+ / B100-FAN_T.FLOW NANO
(with built-in fan).