Installation and Operations Guide
|
MS/TP Microset II
32
LTBT-MSTPMS2IOG Rev. 02 © Honeywell
Vacant mode offers a temporary housekeeping override function. Housekeeping
can press the right
UP button to activate the override, which sets the timer to the
override limit (AV-97).
Housekeeping override operation
The LCD displays the override time remaining. The unit controls to occupied
setpoints while the override timer (AV-98) is non-zero.
Housekeeping can press the right
DOWN button to cancel the override. The timer
can’t restart until it has timed down or been canceled. The setpoint is not
adjustable.
M8—Hotel, Fan, Rented
Set BVs 64, 80, and 81 ON. Operation depends on whether the fan is running or
stopped.
This mode’s counterpart is M9, which is activated by setting BV-64 OFF.
Activate housekeeping
override
Cancel housekeeping
override
Housekeeping override
time remaining in mm:ss