p-2 Introduction
mounted within the drive units allow for the connection of remote operator
devices, I/O signals, etc.
Note: NEMA Type 1 is the standard feature; and NEMA Type 1 with unit
door area gaskets and door fan filters is available as an option.
A variety of available options provide increased unit functionality. The
following drive units are available:
Plug-In Drive Units
The basic standard plug-in drive unit includes:
the selected drive, mounted and wired in an MCC bucket
a fused-disconnect switch with an operator mechanism and appropriate
fuses
power and ground stabs for connecting to bus structure
stab-to-disconnect wiring
output common-mode chokes
a unit support pan
a vented door with fan(s), if appropriate
Note: MCC units that contain plug-in buckets come standard with
manual, vertical bus shutters.
Frame-Mounted Drive Units
The basic standard frame-mounted drive unit includes:
the selected drive, mounted and wired on a panel-mounted assembly
a fused-disconnect switch with an operator mechanism and appropriate
fuses
bus-to-disconnect wiring
output common-mode chokes
a vented door with fan(s), if appropriate
Drive Frames Unit Type
1336 A, B, C plug-in
D, E, F, G roll-out
PowerFle 0, 1, 2, 3 plug-in
4, 5, 6, 9 frame-mounted

Related product manuals