Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016 57
Install the Module Chapter 3
As shown in the cell with value set in bold, the maximum input +24V DC 
power current through the male power connectors in the daisy chain is 6.5 A. 
This value is less than 10 A, so this system is adequate. The I
IP
 value for a 
module in this system or any daisy chained system cannot exceed 10 A. If the 
value exceeds 10 A, the system fails to meet the maximum current requirement 
for the module. The maximum current requirement is the maximum current 
that any pin on the power connectors can carry, which is 10 A.
The output +24V DC power current that is required for a module in the daisy 
chain can be estimated as described here.
I
OP
 ~ I
OPM
 + I
SO
 + I
SNSO
 + I
OPDC
Where:
I
OP
 is the output +24V DC power current through the male power connector 
of the module.
I
OPM
 is the output +24V DC power current required by the module itself  
(with no safety output load current).
I
SO
 is the total safety output load current for safety outputs N. Modules with 
bipolar safety outputs enter values only in the even numbered I
SO
 table 
locations. Modules with sourcing-only safety outputs enter values in all ISO 
table locations.
I
SNSO
 is the total sensor output load current for the Output +24V DC power 
output pins (pin 1 in the output I/O connectors).
Table 14 - Input +24V DC Power Calculation
Value Module 1 Module 2 Module 3 Module 4
I
IPDC
4.875 A 3.250 A 1.625 A 0.000 A
I
IPM
0.175 A 0.175 A 0.175 A 0.175 A
I
TO0
0.005 A 0.005 A 0.005 A 0.700 A
I
TO1
0.005 A 0.005 A 0.005 A 0.700 A
I
TO2
0.005 A 0.005 A 0.700 A 0.005 A
I
TO3
0.005 A 0.005 A 0.700 A 0.005 A
I
TO4
0.005 A 0.700 A 0.005 A 0.005 A
I
TO5
0.005 A 0.700 A 0.005 A 0.005 A
I
TO6
0.700 A 0.005 A 0.005 A 0.005 A
I
TO7
0.700 A 0.005 A 0.005 A 0.005 A
I
TO8
0.005 A 0.005 A 0.005 A 0.005 A
I
TO9
0.005 A 0.005 A 0.005 A 0.005 A
I
TO10
0.005 A 0.005 A 0.005 A 0.005 A
I
TO11
0.005 A 0.005 A 0.005 A 0.005 A
I
IP
6.500 A 4.875 A 3.250 A 1.625 A