64 Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
Chapter 4 Wiring Examples
Wiring Examples for Safety 
Categories
Read this chapter for information about wiring and safety categories. See 
Table 21
 for more information on input device connection methods and their 
safety categories.
Table 21 - Input Device Connection Methods and Safety Categories
Connected Device Test Pulse 
from Test 
Output
Connection Schematic Diagram Safety 
Category
Maximum 
Performance 
Level
Reset switch No Connect the switch 
between I0 and T0. T0 
must be configured as 
24V power supply.
–C
Connect the switch 
between 24V DC and I0.
–C
Single-channel safety 
device
Yes Connect the switch 
between I0 and T0
2D
I0 I1 T0 T1
1
4
5
2
3
1791ES Modules
1732ES Modules
1 - Test Output 1
2 - Input 1
3 - Input Common
4 - Input 0
5 - Test Output 0
24V DC
24V DC
1791ES Modules
1732ES Modules
1 - Test Output 1
2 - Input 1
3 - Input Common
4 - Input 0
5 - Test Output 0
1
4
5
2
3
Only 1732ES Modules
1 - Test Output 1
2 - Input 1
3 - Input Common
4 - Input 0
5 - Test Output 0