62 Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
Chapter 3 Install the Module
Table 20 - Recommended I/O Connector Cables
See http://www.ab.com/en/epub/catalogs/6005557/6005561/6125318/
8613745/8613769/8613771/Introduction.html for additional information.
Label the IP Address and Device Connections
The 1732ES module ships with 12 white labels that you can use to identify the 
IP address of the module, and the input and output connections. There are six 
areas on the module to place the labels, with six additional labels that can be 
used if the IP address or device connections change.
Use a pen or indelible marker with a fine tip to write on the labels. You can also 
use a printing device to print the data onto the label. Contact a Brady 
representative at http://www.bradyid.com
 and ask about printer compatibility 
for part number PTLEP-171-593.
Description Cat. No.
M12 right-angle male to flying leads cordset  889D-E5AC-2
(1)
(1) Replace -2 (2 m [6.6 ft]) with -5 (5 m [16.4 ft]) or -10 (10 m [32.8 ft]) for additional standard cable lengths.
M12 straight-male to flying leads cordset  889D-M5AC-2
(1)
M12 right-angle male to straight female patchcord 889D-F5ACDE-2
(2)
(2) Replace -2 (2m [6.6 ft]) with -OM3 (0.3 m [1.0 f t]), -1 (1 m [3.3 ft]), -5 (5 m [16.4 ft]), or -10 (10 m [32.8 ft]) for additional 
standard cable lengths.
M12 straight male to straight female patchcord 889D-F5ACDM-2
(2)
IMPORTANT: Be sure that the 
surface of the module is clean 
and dry before you apply the 
labels to the module.
Apply two labels here to identify 
the IP address of the module.
Apply one label between each 
pair of I/O connectors.
On the left side of the label, 
identify the signal assignment to 
the I/O connection on the left 
side of the module.
On the right side of the label, 
identify the signal assignment to 
the I/O connection on the right 
side of the module.