EasyManuals Logo

Allen-Bradley 1734-IE2C User Manual

Allen-Bradley 1734-IE2C
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
POINT I/O 2 Current and 2 Voltage Input Analog Modules 19
Publication 1734-IN027C-EN-E - October 2016
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating EC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating EC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions CISPR11
Group 1, Class A
ESD immunity IEC6100-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 30…2000 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
EFT/B immunity IEC 61000-4-4:
±3 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5:
±2 kV line-earth (CM) on shielded ports
Conducted RF immunity IEC61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz