EasyManua.ls Logo

Allen-Bradley 1734-IE2C - Environmental Specifications

Allen-Bradley 1734-IE2C
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
POINT I/O 2 Current and 2 Voltage Input Analog Modules 19
Publication 1734-IN027C-EN-E - October 2016
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating EC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating EC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions CISPR11
Group 1, Class A
ESD immunity IEC6100-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 30…2000 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
EFT/B immunity IEC 61000-4-4:
±3 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5:
±2 kV line-earth (CM) on shielded ports
Conducted RF immunity IEC61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz

Related product manuals