90 Rockwell Automation Publication 1734-UM013N-EN-P - September 2017
Chapter 5 Configure the Module in a GuardLogix Controller System
2. Assign the Point Operation Type.
When you choose Equivalent or Complementary, you must also assign a 
Discrepancy Time.
A discrepancy time setting of 0 ms means that the channels in a dual 
configuration can be discrepant for an infinite amount of time without a 
fault being declared.
For a discrepancy time setting of 0 ms, the evaluated status of the inputs 
still goes to the safe state due to a ‘cycle inputs’ required condition. 
However, with a 0 ms discrepancy time setting, a fault is not declared.
A ‘cycle inputs’ required condition occurs when one input terminal goes 
from its normal Active->Inactive->Active state while the other input 
terminal remains in its normal Active state. Even though no fault is 
declared, the inputs must be cycled through the safe state before the 
evaluated status of the inputs can return to the Active state. When in a 
‘cycle inputs’ required condition, the logical state does not necessarily 
match the voltage at the terminals.
Choose Description
Single Inputs are treated as single channels. 
Dual-channel safety inputs can be configured as two individual single channels. 
This configuration does not affect pulse tests because it is handled on an 
individual channel basis.
IMPORTANT: Use single-channel mode when you intend to use the GuardLogix 
safety application instructions.
Equivalent Inputs are treated as a dual-channel pair. The channels must match within the 
discrepancy time or an error is generated.
Complementary Inputs are treated as a dual-channel pair. They must be in opposite states within 
the discrepancy time or an error is generated.
Configuring discrepancy time on safety I/O modules masks input 
discrepancies that the controller safety instructions detect. The 
controller reads status to obtain this fault information.