Appendix C Use Ladder Logic To Perform Run Time Services and Reconfiguration
The input point (point 0) must have Change of State enabled. Otherwise, 
the timestamp will not update when the point transitions. 
Once Change of State has been detected, the value in the Delay tag is 
added to the input timestamp and sent to the output module's timestamp 
using a COP instruction. This causes the output module to apply its 
output at a time equal to the time that the input changed state plus the 
Delay time.
The final COP instruction updates LastInputTimestamp in preparation 
for the next change of state.
• Rung 4 is the standard XIC-OTE rung that controls the output point 
based on the input point. The only difference is that the output module is 
configured for scheduled outputs. The outputs will not get applied until 
the scheduled time has occurred.
The Controller Tags dialog box below shows examples of the tags created in 
ladder logic.