Environmental Conditions (continued)
Shock IEC60068-2-27:1987, Test Ea (Unpackaged shock,
ES#002)
Operating 15g
Non-operating 30g
Emissions CISPR 11
Group 1, Class A
ESD Immunity IEC 61000-4-2
6kV contact discharges
15kV air discharges
Radiated RF Immunity IEC 61000-4-3
10V/m with 1kHz sine-wave 80%AM from 30MHz to
2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
EFT/B Immunity IEC 61000-4-4
±4kV at 2.5kHz on power ports
±2kV at 5kHz on signal ports
Surge Transient Immunity IEC 61000-4-5
+
2kV line-earth (CM) on shielded ports
Conducted RF Immunity IEC 61000-4-6
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz
Enclosure Type Rating None (open-style)
Certifications
(where product is marked)
UL UL Listed Industrial Control Equipment
CSA CSA Certified Process Control Equipment
CSA CSA Certified Process Control Equipment
for Class I, Division 2 Group A,B,C,D
Hazardous Locations
FM FM Approved Equipment for use in Class I
Division 2 Group A,B,C,D Hazardous
Locations
CE
(3)
European Union 89/336/EEC EMC Directive,
compliant with:
EN 50081-2; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
C-Tick
(3)
Australian Radiocommunications Act,
compliant with:
AS/NZS 2064; Industrial Emissions
Spare Allen-Bradley Parts