14 ControlLogix Analog (10V) Output Module
Publication 1756-IN035C-EN-P - October 2000
Additional Notes
The ControlLogix system must be mounted within a suitable enclosure to
prevent personal injury resulting from accessibility to live parts. The interior of
this enclosure must be accessible only by the use of a tool.
This industrial control equipment is intended to operate in a Pollution Degree
2 environment, in overvoltage category II applications, as defined in IEC
publication 664A, at altitudes up to 2000 meters without derating.
Module Conversion Method R-Ladder DAC, monotonicity with no missing codes
Capacitive Load <1 µFd
RTB Screw Torque (NEMA) 7-9 inch-pounds (0.8-1Nm)
Module Keying (Backplane) Electronic
RTB Keying User defined
Field Wiring Arm and Housing
20 Position RTB (1756-TBNH or TBSH)
1
Environmental Conditions
Operating Temperature
Storage Temperature
Relative Humidity
0 to 60°C (32 to 140°F)
-40 to 85°C (-40 to 185°F)
5 to 95% noncondensing
Conductors Wire Size
Category
22-14 gauge (2mm
2
) stranded
1
3/64 inch (1.2mm) insulation maximum
2
2, 3
Screwdriver Width for RTB 5/16 inch (8mm) maximum
Agency Certification
(when product or
packaging is marked)
1
Maximum wire size will require extended housing - 1756-TBE.
2
Use this conductor category information for planning conductor routing as described in the system
level installation manual.
3
Refer to publication 1770-4.1 “Industrial Automation Wiring and Grounding Guidelines’.
Marked for all applicable directives
Approved Class I, Division 2, Group A, B, C, D
Certified Process Control Equipment
Certified Class I, Division 2, Group A, B, C, D
Marked for all applicable acts
N223
Listed Industrial Control Equipment