ControlLogix Redundant Power Supply 23
Publication 1756-IN573C-EN-P - October 2003
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp
Heat):
5 to 95% non-condensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
2g @ 10-500Hz
Operating Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30g
Non-operating Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50g
Emissions CISPR 11:
Group 1, Class A
ESD Immunity IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to
1000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
EFT/B Immunity IEC 61000-4-4:
±4kV at 2.5kHz on power ports
Surge Transient Immunity IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on AC power
ports
Conducted RF Immunity IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz
Enclosure Type Rating None (open-style)
Voltage Variation IEC 61000-4-11:
30% dips for 1 period at 0° & 180° on AC supply ports
60% dips for 5 & 50 periods on AC supply ports
±10% fluctuations for 15min on AC supply ports
>95% interuptions for 250 periods on AC supply ports"
"60% dips for 100ms on DC supply ports
100% dips for 50ms on DC supply ports
±20% fluctuations for 15min on DC supply ports
5sec interruptions on DC supply ports
1756-PA75R/A 1756-PB75R/A
Allen-Bradley HMIs