ControlNet Modular Repeater Medium Distance Fiber Module 17
Publication 1786-IN011B-EN-P - October 2000
Specifications
Specification Range
Communication Rate 5M bits/s
Operation Voltage
Class 2 operational power is provided from 1786-RPA at 5 V dc
(2)
Backplane Power Requirements 400 mA maximum
Indicators Channel 1 Status - Green
Channel 2 Status - Green
Environmental Conditions This product must be mounted within a suitable system enclosure
to prevent personal injury resulting from accessibility to live parts.
The interior of this enclosure must be accessible only by the use of
a tool.
OperatingTemperature
0 to 60
o
C (32 to 125
o
F)
Storage Temperature
-40 to 85
o
C (-40 to 185
o
F)
Pollution This industrial control equipment is intended to operate in a
Pollution Degree 2 environment, in overvoltage category II
applications, (as defined in IEC publication 664A) at altitudes up to
2000 meters without derating.
Relative Humidity 5 to 95% non-condensing
Shock Operating
Non-operating
30 g peak acceleration, 11(
± 1)ms pulse width
50 g peak acceleration, 11(
± 1)ms pulse width
Vibration Tested 5 g @ 10-500Hz per IEC 68-2-6