EasyManua.ls Logo

Allen-Bradley D Series - Acceptable Chassis Combinations

Allen-Bradley D Series
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addressing Modes for Your Remote I/O
Chapter 3
3-24
Not all chassis combinations are acceptable in making I/O rack number
assignments. For example, a 1771-A4B I/O chassis cannot complete an
assigned I/O rack number that starts in a 1771-A1 I/O chassis. Refer to
Table 3.B for acceptable beginning I/O group numbers when making your
I/O rack number assignments.
Table 3.B
Acceptable
Beginning I/O Group Numbers
If you select: and:
The beginning I/O group
number can be:
2slot addressing 4slot chassis 0, 2, 4, 6
8slot chassis 0, 2, 4
12slot chassis 0, 2
16slot chassis 0
1slot addressing 4slot chassis 0, 2, 4, 6
8slot chassis 0, 2, 4, 6
12slot chassis 0, 2, 4,
16slot chassis 0
1/2slot addressing 4slot chassis 0
8slot chassis 0
12slot chassis 0
16slot chassis 0
Acceptable
Chassis
Combinations

Related product manuals