34 Rockwell Automation Publication 440C-WD001C-EN-P - June 2015
Chapter 6 Muting 2-Sensor T-Type Bidirectional
Machine Layout
The material can flow in either direction: to the hazard area from the non-hazard
area or reverse. The shape of the material must be such that it blocks both muting
sensors before it blocks the light curtain. The order in which the muting sensors
are blocked is not critical, but the synchronization time (time between blocking
one sensor and the other sensor) must be met.
Figure 19 - Machine Layout
Schematic
The example schematic is set up to agree with the terminals shown in the
Connected Components Workbench software and the example bill of materials.
Figure 20 - Schematic
Hazard Area Non-hazard Area
Machine
MS1 MS2
LC
Muting Lamp
Material
Conveyor
+24V DC
Muted
Light Curtain
24V DC Com
AB
Pink OSSD A
Grey OSSD B
BlueBlue
Override
Contactors
for Conveyor
Power
Muting
Lamp
05
CR30
020100 03 04
A1 15 20 2116
06
18A2
07
19
08 10 11
12 13 14
09
17
K2K1
Black
Brown
Brown
Blue
Blue
K2
K1
3 4 11 31 3
Black
Brown
Brown
Brown
Brown
Blue
Blue
Muting
Sensor 1
Muting
Sensor 2
3 4 1
6
5
7
21
3