58 Rockwell Automation Publication 440R-UM013E-EN-P - March 2017
Chapter 9 Application and Wiring Examples
The EMD safety relay in Figure 51 is configured for a maximum of a
100-second jog. The single wire safety signal from terminals L11 to L12
enables the EMD safety relay. When enabled, the jog switch can be pressed and
held closed to turn on the EMD safety relay outputs. If the jog button is
released before the 100 second time, the EMD safety relay outputs turn off. If
the jog button is held longer than 100 seconds, the EMD safety relay outputs
only turn on for 100 seconds.
Figure 51 - EMD - Jog
SI Safety Relay
(Cat.No.440R-S12R2)
The SI safety relay monitors a gate interlock with mechanical contacts in
Figure 52
. The SI safety relay is configured for automatic reset. When the gate
is closed, the SI safety relay outputs turn on if contactors K1 and K2 are already
off. The Start button can then be pressed to turn on contactors K1 and K2.