86 Rockwell Automation Publication 440R-UM013E-EN-P - March 2017
Chapter 11 Troubleshooting
EMD Expansion Relay B1/B2
Inputs (Step 7)
Figure 86 shows the waveform from B1 to B2. This waveform is the same as the
single wire safety waveform. The waveform is present only when the output of
the EMD expansion relay is ON. With a digital multimeter, the voltage
measures 8…9V DC.
If the B1 status indicator is on, but no voltage is read, your expansion relay
must be replaced.
Figure 86 - The B1-B2 Waveform When the EMD Output is ON
TIP For more information on retriggerable inputs, see page 33.