Rockwell Automation Publication 2080-UM005B-EN-E - March 2015 127
Troubleshooting Appendix B
0xF005 The user program failed an integrity check while the
Micro800 controller was in Run mode.
Perform one of the following:
• Cycle power on your Micro800 controller. Then, download your program
using Connected Components Workbench and start up your system.
• Refer to Wiring Requirements and Recommendation
on page 29.
0xF006 The user program is incompatible with the Micro800
controller’s firmware revision.
Perform one of the following:
• Upgrade the Micro800 controller’s firmware revision using ControlFlash.
• Contact your local Rockwell Automation technical support representative
for more information about firmware revisions for your Micro800
controller. For more information on firmware revision compatibility, go to
http://www.rockwellautomation.com/support/firmware.html
0xF010 The user program contains a function/function block that
is not supported by the Micro800 controller.
Perform the following:
1. Modify the program so that all functions/function blocks are supported by
the Micro800 controller.
2. Build and download the program using Connected Components
Workbench.
3. Put the Micro800 controller into Run mode.
0xF014 A memory module memory error occurred. Reprogram the memory module. If the error persists, replace the memory
module.
0xF015 An unexpected software error occurred. Perform the following:
1. Cycle power on your Micro800 controller.
2. Build and download your program using Connected Components
Workbench, and then reinitialize any necessary data.
3. Start up your system.
Refer to Wire Your Controller on page 29.
0xF016 An unexpected hardware error occurred. Perform the following:
1. Cycle power on your Micro800 controller.
2. Build and download your program using Connected Components
Workbench, and then reinitialize any necessary data.
3. Start up your system.
Refer to Wire Your Controller on page 29.
0xF017 An unexpected software error occurred due to
unexpected hardware interrupt.
If the system variable __SYSVA_USER_DATA_LOST has
been set, the controller will be able to recover the user
program, but the user data will be cleared. If not, the
Micro800 controller program will be cleared.
Perform one of the following:
• Download the program using Connected Components Workbench
software.
• Transfer the program using the memory module restore utility or the
microSD card.
If the fault persists, contact your local Rockwell Automation technical
support representative. For contact information, see:
http://support.rockwellautomation.com/MySupport.asp
.
0xF018 An unexpected software error occurred due to SPI
communication failure.
If the system variable __SYSVA_USER_DATA_LOST has
been set, the controller will be able to recover the user
program but the user data will be cleared. If not, the
Micro800 controller program will be cleared.
Perform one of the following:
• Download the program using Connected Components Workbench
software.what
• Transfer the program using the memory module restore utility or the
microSD card.
If the fault persists, contact your local Rockwell Automation technical
support representative. For contact information, see:
http://support.rockwellautomation.com/MySupport.asp
.
OxF019 An unexpected software error occurred due to memory or
other controller resource issue.
Perform one of the following:
• Download the program using Connected Components Workbench
software.
• Transfer the program using the memory module restore utility or the
microSD card.
If the fault persists, contact your local Rockwell Automation technical
support representative. For contact information, see:
http://support.rockwellautomation.com/MySupport.asp
.
List of Error Codes for Micro800 Controllers
Error Code Description Recommended Action