224 Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
Appendix A Specifications
Micro850 48-Point Controllers
General Specifications
Attribute 2080-LC50-48AWB 2080-LC50-48QWB 2080-LC50-48QVB 2080-LC50-48QBB
Number of I/O 48 (28 inputs, 20 outputs)
Dimensions (HxWxD) 90 x 238 x 80 mm (3.54 x 9.37 x 3.15 in.)
Shipping weight, approx. 0.725 kg (1.60 lb)
Wire size 0.2…2.5 mm
2
(24…14 AWG) solid copper wire or
0.2…2.5 mm
2
(24…14 AWG) stranded copper wire
rated @ 90 °C (194 °F) insulation max
Wiring category
(1)
2 – on signal ports
2 – on power ports
2 – on communication ports
Wire type Use Copper Conductors only
Terminal screw torque 0.4…0.5 Nm (3.5…4.4 lb-in.)
(using a 0.6 x 3.5 mm flat-blade screwdriver)
Input circuit type 120V AC 12/24V sink/source (standard)
24V sink/source (high-speed)
Output circuit type Relay 24V DC sink
(standard and high-speed)
24V DC source
(standard and high-speed)
Power consumption, max 11 W – without plug-in modules and expansion I/O modules
33 W –with plug-in modules and expansion I/O modules
Power supply voltage range 20.4…26.4V DC Class 2
I/O rating Input:
120V AC, 16 mA
Output:
2 A, 240V AC,
2A, 24V DC
Input:
24V, 8.8 mA
Output:
2 A, 240V AC,
2A, 24V DC
Input:
24V, 8.8 mA
Output:
24V DC, 1 A per point
(surrounding air temperature 30 °C)
24V DC, 0.3 A per point
surrounding air temperature 65 °C)
Insulation stripping length 7 mm (0.28 in)
Enclosure type rating Meets IP20
Pilot duty rating C300, R150 –
Isolation voltage 250V (continuous),
Reinforced Insulation Type,
Output to Aux and Network,
Inputs to Outputs.
Type tested for 60 s @
3250V DC Output to Aux and
Network, Inputs to Outputs.
150V (continuous),
Reinforced Insulation Type
Input to Aux and Network
Type tested for 60 s @
1950V DC Input to Aux and
Network.
250V (continuous),
Reinforced Insulation Type,
Output to Aux and Network,
Inputs to Outputs
Type tested for 60 s @
3250V DC Output to Aux and
Network, Inputs to Outputs
50V (continuous),
Reinforced Insulation Type,
Input to Aux and Network
Type tested for 60 s @ 720V
DC, Inputs to Aux and
Network
50V (continuous), Reinforced Insulation Type, I/O to Aux
and Network, Inputs to Outputs
Type tested for 60 s @ 720V DC, I/O to Aux and Network,
Inputs to Outputs.
North American temp code T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.