Process Control Instruction 19-25
Verifying the Scaling of Your Continuous System
To ensure that your process is linear, and that your equipment is properly
connected and scaled, do the following:
1. Place the PID instruction in MANUAL and enter the following
parameters:
type:
0
for MinS
type:
100
for MaxS
type:
0
for CO%
2. Enter the REM RUN mode and verify that PV=0.
3. Type:
20
in CO%
4. Record the PV = _______
5. Type:
40
in CO%.
6. Record the PV = _______
7. Type:
60
in CO%.
8. Record the PV = _______
9. Type:
80
in CO%.
10. Record the PV = _______
11. The values you recorded should be offset from CO% by the same
amount. This proves the linearity of your process. The following
example shows an offset progression of fifteen.
CO 20% = PV 35%
CO 40% = PV 55%
CO 60% = PV 75%
CO 80% = PV 95%
If the values you recorded are not offset by the same amount:
Either your scaling is incorrect, or
the process is not linear, or
your equipment is not properly connected and/or configured.
Make the necessary corrections and repeat steps 2-10.

Table of Contents

Other manuals for Allen-Bradley micrologix 1500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley micrologix 1500 and is the answer not in the manual?

Allen-Bradley micrologix 1500 Specifications

General IconGeneral
Processor Type16-bit
Programming LanguageLadder Logic
MountingDIN rail or panel mount
Programming SoftwareRSLogix 500
Communication PortsRS-232
Power Supply24V DC
Operating Temperature0°C to 55°C (32°F to 131°F)
Controller TypeProgrammable Logic Controller (PLC)

Related product manuals