2-200 Start-Up
Figure 2.40 PowerFlex 700 Vector Control Option Startup (10)
Start-Up
Frequency-V/Hz
Enter value for
Break Voltage
10.0 Hz
x.x < y.y
Start-Up
Frequency-V/Hz
Enter value for
Max Voltage
10.0 V
x.x < y.y
Start-Up
1. Motor Control
Enter choice of
Control:
<Speed>
Torque
More info
Flux Vector Start Up (Motor Control Select)
Start-Up
1. Motor Control
This section
selects the type
of Motor Control
the drive will
use.
1-0 1-1
1-6
Start-Up
Frequency-V/Hz
Enter value for
Start Boost
10.0 V
x.xxxx < y.yyyy
Start-Up
Frequency-V/Hz
Enter value for
Break Frequency
10.0 Hz
x.xxxx < y.yyyy
1-3
1-5
Go to 0-1
2. Motr Dat/Ramp
1-9
Start-Up
Frequency-V/Hz
Enter value for
Run Boost
10V
xx.x < yy.y
1-8
1-4
Start-Up
Speed-SVC
Enter value for
Max Voltage
10.0 V
x.x < y.y
1-10
YES-Speed path-
Set #88 to 1
Start-Up
Speed-SVC
Enter value for
Encoder PPR
1024
1-11
Start-Up
Frequency-V/Hz
Select Motor
Control Mode
<V/Hz-Fan/Pump>
V/Hz-Custom
V/Hz-Multi Motor
SV-No regulation
Start-Up
Speed-SVC
Control selected
is FOC Speed
Regulate.
Start-Up
Speed-SVC
Control selected
is Speed/SVC
with Slip Comp
V/Hz
Custom/Multi
Motor - Set
param #53 to '2'
& #80 to '0'
Start-Up
Frequency-V/Hz
Select V/Hz
Parameters.
<Standard V/Hz>
Custom V/Hz
Start-Up
Frequency-V/Hz
Control selected
is Freq/V/Hz.
Standard
Start-Up
Frequency-V/Hz
Control selected
is Frequency/SV
no Slip Comp
Sensorless
Vector - set param #53
to '0' & #80 to '0'
Start-Up
Frequency-V/Hz
Control selected
is Freq/Fan/Pump
no Slip Comp
Fan/Pump -
Set param
#53 to '3' &
#80 to '0'
1-12
1-13
1-14
1-15
1-16
1-17
1-18
1-19
Torque-
Yes
Start-Up
Torque-FOC
An Encoder is
required for the
Torque Control
option. Select
another Motor
Control option
or install an
encoder.
Torque- No
Go to 1-1
Start-Up
Frequency-V/Hz
Control selected
is Freq/Custom.
1-20
Start-Up
Torque-FOC
Control selected
is Torque/FOC
Torque Regulate
1-7
Torque path
Trq
Regulate
Set #88
to 2
1-21
Start-Up
Torque-FOC
Select Torque
Regulate option:
<Torque Regulate>
Min Torque/Speed
Max Torque/Speed
Sum Torque/Speed
Absolute
1-22
Start-Up
Speed-SVC
Enter choice of
Speed Units
<V/Hz>
RPM
1-2
Start-Up
Torque
Is an encoder
present?
<Yes>
No
1-23
Start-Up
Torque-FOC
Control selected
is Torque/FOC
Min Torque/Speed
Start-Up
Torque-FOC
Control selected
is Torque/FOC
Max Torque/Speed
1-24
1-25
Min Torque/
Speed -
Set #88 to 3
Max
Trq/Speed -
Set #88 to 4
Start-Up
Torque-FOC
Control selected
is Torque/FOC
Sum Torque/Speed
Sum Trq/Speed-
Set #88 to 5
Start-Up
Torque-FOC
Control selected
is Torque/FOC
Absolute
Absolute-
Set #88
to 6
Torque
Start-Up
Speed-SVC
Use Speed-SVC
for applications
requiring speed
regulation.
Start-Up
Speed
Is an encoder
present?
<Yes>
No
Speed
Start-Up
Frequency-V/Hz
Select Motor
Control Mode
<SVC-common>
V/Hz
More info
NO
Custom
V/Hz

Table of Contents

Other manuals for Allen-Bradley PowerFlex 70

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 70 and is the answer not in the manual?

Allen-Bradley PowerFlex 70 Specifications

General IconGeneral
Input Voltage200-240V AC, 380-480V AC, 500-600V AC
Frequency Range0 - 400 Hz
Humidity5% to 95% non-condensing
Output Voltage0 to Input Voltage
Control MethodsSensorless Vector Control
CommunicationsEthernet/IP, DeviceNet, ControlNet
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Ground Fault
Operating Temperature0°C to 50°C (32°F to 122°F)
Storage Temperature-40°C to 70°C (-40°F to 158°F)
Enclosure RatingIP20, NEMA Type 1