Stop Modes 2-203
5. Ramp To Hold is selected by setting [Stop Select x]. The drive will
ramp the frequency to zero based on the deceleration time programmed
into [Decel Time 1/2]. Once the drive reaches zero hertz, a DC Injection
holding current is applied to the motor. The level of current is set in [DC
Brake Level].
In this mode, the braking is applied Continuously. [DC Hold Time] has
no effect in this mode. Braking will continue until one of the following
events occur:
The Enable Input is opened, or . . .
A Start command is re-issued.
Again, caution must be exercised to not overheat the motor by applying
excess voltage and/or for excess time, particularly if the motor is not
rotating.
DC
Hold Level
Time
Output Voltage
Output Voltage
Output Current
Output Current
Motor Speed
Output Voltage
Output Current
Motor Speed
Re-issuing a
Start Command
Stop
Command
Zero
Command
Speed

Table of Contents

Other manuals for Allen-Bradley PowerFlex 70

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 70 and is the answer not in the manual?

Allen-Bradley PowerFlex 70 Specifications

General IconGeneral
Input Voltage200-240V AC, 380-480V AC, 500-600V AC
Frequency Range0 - 400 Hz
Humidity5% to 95% non-condensing
Output Voltage0 to Input Voltage
Control MethodsSensorless Vector Control
CommunicationsEthernet/IP, DeviceNet, ControlNet
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Ground Fault
Operating Temperature0°C to 50°C (32°F to 122°F)
Storage Temperature-40°C to 70°C (-40°F to 158°F)
Enclosure RatingIP20, NEMA Type 1

Related product manuals