EasyManuals Logo

Allen-Bradley powerflex 700 Technical Data

Allen-Bradley powerflex 700
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
PowerFlex 700 Technical Data
20B-TD001F-EN-P 27
Frames 7…10
Vector Control Option (Frames 7…10)
No. Signal
Factory
Default
Description
Related
Param.
1 Analog In 1 (–)
(1)
(1)
Important: 0-20mA operation requires a jumper at terminals 17 & 18 (or 19 & 20). Drive damage may occur if
jumper is not installed.
(2)
(2)
These inputs/outputs are dependant on a number of parameters (see “Related Parameters”).
Isolated
(3)
, bipolar, differential, ±10V/4-20mA, 11
bit & sign, 88k ohm input impedance. For 4-20mA,
a jumper must be installed at terminals 17 & 18 (or
19 & 20).
(3)
Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides
high common mode immunity.
320 -
327
2 Analog In 1 (+)
(1)
3 Analog In 2 (–)
(1)
4 Analog In 2 (+)
(1)
5 Pot Common For (+) and (–) 10V pot references.
6 Analog Out 1 (–)
(2)
Bipolar (current output is not bipolar), ±10V/4-
20mA, 11 bit & sign, voltage mode - limit current to
5 mA. Current mode - max. load resistance is 400
ohms.
340 -
347
7 Analog Out 1 (+)
8 Analog Out 2 (–)
9 Analog Out 2 (+)
10 HW PTC Input 1 1.8k ohm PTC, Internal 3.32k ohm pull-up resistor 238 259
11 Digital Out 1 – N.C.
(4)
(4)
Contacts in unpowered state. Any relay programmed as Fault or Alarm will energize (pick up) when power is
applied to drive and deenergize (drop out) when a fault or alarm exists. Relays selected for other functions will
energize only when that condition exists and will deenergize when condition is removed.
Fault Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10mA
380 -
391
12 Digital Out 1 Common
13 Digital Out 1 – N.O.
(4)
NOT Fault
14 Digital Out 2 – N.C.
(4)
NOT Run
15 Digital Out 2/3 Com.
16 Digital Out 3 – N.O.
(4)
Run
17 Current In Jumper
(1)
Analog In 1
Placing a jumper across terminals 17 & 18 (or 19
& 20) will configure that analog input for current.
18
19 Current In Jumper
(1)
Analog In 2
20
21 –10V Pot Reference 2k ohm minimum load.
22 +10V Pot Reference
23 HW PTC Input 2 See above
24 +24VDC
(5)
Drive supplied logic input power.
(5)
(5)
150mA maximum Load. Not present on 115V versions.
25 Digital In Common
26 24V Common
(5)
Common for internal power supply.
27 Digital In 1 Stop - CF 115V AC, 50/60 Hz
- Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC
24V DC
- Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC
11.2 mA DC
361 -
366
28 Digital In 2 Start
29 Digital In 3 Auto/Man.
30 Digital In 4 Speed Sel 1
31 Digital In 5 Speed Sel 2
32 Digital In 6/Hardware
Enable, see pg. 28
Speed Sel 3
33 Digital Out 4 – N.C. Fault Dedicated fault output - Not user configurable.
Relay will energize (pick up) when power is
applied to drive and deenergize (drop out) when a
fault exists. See Terminals 11…16 for specs.
34 Digital Out 4 Common
35 Digital Out 4 – N.O. NOT Fault
PS+ Aux. Control Power (+)
PS- Aux. Control Power (-)
PE PE Ground PE Ground
PE PE Ground PE Ground
1

Other manuals for Allen-Bradley powerflex 700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley powerflex 700 and is the answer not in the manual?

Allen-Bradley powerflex 700 Specifications

General IconGeneral
SeriesPowerFlex 700
CategoryAC Drive
Input Voltage200-240V AC, 380-480V AC, 500-600V AC
EnclosureType 1
Control MethodSensorless Vector
CommunicationEtherNet/IP, ControlNet, DeviceNet, PROFIBUS DP, Modbus

Related product manuals