Electrical Requirements
90
©
Copyright, Alliance Laundry Systems LLC - DO NOT COPY or TRANSMIT Part No. 70458301ENR7
230-240V/50Hz/1ph L1, Neutral, and
ground
58 N/A 80A – 1 pole 4 (25)
200-208V/60Hz/3ph L1, L2, L3, and
ground
37 37 50A* – 3 pole 6 (16)
200V/50Hz/3ph L1, L2, L3, and
ground
36 36 50A* – 3 pole 6 (16)
230-240V/50Hz/3ph L1, L2, L3, and
ground
33 N/A 50A* – 3 pole 6 (16)
240V/60Hz/3ph L1, L2, L3, and
ground
33 33 50A* – 3 pole 6 (16)
380V/50 or
60Hz/3ph
L1, L2, L3, and
ground
20 20 25A* – 3 pole 10 (6)
400-415V/50Hz/3ph L1, L2, L3, and
ground
18 18 25A* – 3 pole 10 (6)
440V/60Hz/3ph L1, L2, L3, and
ground
17 N/A 25A* – 3 pole 10 (6)
460-480V/60Hz/3ph L1, L2, L3, and
ground
16 16 25A* – 3 pole 10 (6)
* 3 Phase machines should not have fuses, breakers only.
N/A = Not Applicable
Table 18
21 kW Classic Line 030 Series Electric Models
Serial Plate Amps Recommended CircuitSerial Plate Voltage Terminal Block
Connections
Required
Non-reversing Reversing Breaker Rating Wire Size AWG
(mm
2
)
208V/60Hz/1ph L1, L2, Neutral,
and ground
108 N/A 150A – 2 pole 1/0 (50)
240V/60Hz/1ph L1, L2, Neutral,
and ground
94 N/A 125A – 2 pole 1 (35)