Electrical Requirements
Part No. 70458301ENR7
©
Copyright, Alliance Laundry Systems LLC - DO NOT COPY or TRANSMIT 91
200V/60Hz/1ph L1, Neutral, and
ground
108 N/A 150A – 1 pole 1/0 (50)
200V/50Hz/1ph L1, Neutral, and
ground
105 N/A 150A – 1 pole 1/0 (50)
230-240V/50Hz/1ph L1, Neutral, and
ground
95 N/A 125A – 2 pole 1 (35)
200-208V/60Hz/3ph** L1, L2, L3, and
ground
62 62 80A* – 3 pole
200V/50Hz/3ph** L1, L2, L3, and
ground
60 60 80A* – 3 pole 4 (25)
230-240V/50Hz/3ph** L1, L2, L3, and
ground
55 N/A 70A* – 3 pole 4 (25)
240V/60Hz/3ph** L1, L2, L3, and
ground
54 54 70A* – 3 pole 4 (25)
380V/50 or 60Hz/3ph** L1, L2, L3, and
ground
33 33 45A* – 3 pole 8 (10)
400-415V/50Hz/3ph** L1, L2, L3, and
ground
31 31 40A* – 3 pole 8 (10)
440V/60Hz/3ph L1, L2, L3, and
ground
29 N/A 40A* – 3 pole 8 (10)
460-480V/60Hz/3ph** L1, L2, L3, and
ground
27 27 35A* – 3 pole 8 (10)
* 3 Phase machines should not have fuses, breakers only.
** These serial plate voltages are only options available on the 30 series electric models.
N/A = Not Applicable
Table 19
12 kW Eco Line 030 Series Electric Models
Serial Plate Voltage Terminal Block
Connections
Required
Serial Plate Amps Recommended Circuit