Conduct routine inspection on the
corrosion of metal components.
(once half a year)
Yearly inspection on the contactor
(auxiliary switch or micro-switch)
and ensure it good mechanical
running.
Check the operation parameters
(especially voltage and insulation).
Check the emergency stop switch
and LCD
Simulate power off and check
whether communication signals
are available during power off.
Check the warning label. If
necessary, please change it in
time.
Notes
After all of the equipments are out of operation, the following notes should be paid attention
to while maintaining:
Related safety standards and specifications should be followed in operation and
maintenance.
Disconnect all the electrical connections so that the equipment would not be powered on.
Wait at least 15 minutes after disconnection in case that the residual voltage of capacitors
down to safe voltage. Use a multimeter to ensure the equipment is completely uncharged.
The amount of maintenance staff should be not less than two while maintaining.
The equipment should be repaired by professional staff and it is strictly forbidden for
maintenance staff to open equipments on their own.
Appropriate protective measures should be taken while maintaining, such as insulated
gloves, shoes, and anti-noise ear plugs.
Usually the location of the storage system is far away from urban areas. Related
emergency rescue measures should be prepared in order to be implemented when
necessary.
Life is priceless. Make sure no one would get hurt first.
When a fire happened in the container, just make sure the fire system is on (should be on),
then leave the container as soon as possible. After running out, make sure all doors are
closed. The fire extinguishing system would automatically work. Do not try to put the fire
out manually.