Subject to change without notice | 83056600cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
The power supply for the heat pump is
equipped with an all-pole miniature circuit-
breaker with at least 3mm contact spacing
(IEC 60947-2).
The level of the tripping current is compliant.
Theheatingcircuitandheatsourceareushed
and vented.
The frost protection of the heat source liquid is
Tecnical Data‘
All shut-off devices of the heating circuit are
open.
All shut-off devices of the heat source are
open.
The pipe systems and components of the
systemareleaktight.
2. Fill out carefully and sign the completion report for
heat pump systems.
3. In Germany and Austria: Send completion
report for heat pump systems and
general checklist to the manufacturer’s
factory customer service department.
In other countries: Send completion report for
heat pump systems and general checklist to the
manufacturer’slocalpartner.
4. Arrange for the heat pump system to be started up
by customer service personnel authorised by the
manufacturer; this is a chargeable service.
5. Ensure that the water supply to the domestic hot
watertankisopen.
11 Maintenance
NOTE
We recommend that you sign a maintenance
agreement with an accredited heating
company.
11.1 Basic principles
The cooling circuit of the heat pump requires no
regular maintenance.
Local regulations– e.g. EU Regulation (EC) 842/2006
–amongotherthings,requireleakchecksbeforehand
and/orforalogbooktobekeptforcertainheatpumps.
Thehermeticleaktightnessandrefrigerantllquantity
arecriteriaforwhetheralogbookhasto be keptand
leaktestsperformedornot,andatwhattimeintervals.
Ensure compliance with local regulations with
regardtothespecicheatpumpsystem.
11.2 Maintenance as required
Yearly, more frequently if necessary:
Checkingandcleaningthecomponentsofthe
heating circuit and the heat source, e.g. valves,
expansion vessels, circulation pumps, lters,
dirt traps.
Checking the function of the safety valve (on
site) for the domestic hot water tank and the
safety valve for the heating circuit.
11.3 Yearly maintenance
Record the quality of the heating water analytically.
Incaseofdeviationsfromthespecications,take
suitable measures without delay.
Clean unit variant with SVGW storage tank (SVGW:
Swiss gas and water association (Schweizerischer
Verein des Gas- und Wasserverbands)):
1. Drain the domestic hot water tank via the drain
valve at the domestic cold water inlet.
2. Ventthedomestichotwatertankandpipesviathe
hot water taps in the apartments.
3. Checkthedomestichotwatertankandcleanvia
thecleaningopeningontheundersideofthetank.
4. Aftercleaning and testing, rell the domestic hot
watertank.
5. Ventthedomestichotwatertankandpipesviathe
hot water taps in the apartments.
11.4 Cleanandushtheevaporator
and condenser
Cleanandushtheevaporator/condenserstrictly
according to the manufacturer's regulations.
After ushing the evaporator/condenser with
chemical cleaning product: Neutralise any
residues and ush the evaporator/condenser
thoroughly with water.