Modbus Integrator's Guide for the CXC HP | 2 - Using Modbus
Table 10. L-ADIO Data Points (continued)
Name Register Format
Temperature Sensor #2 Failure 02:Input Status Boolean
Temperature Sensor #3 Failure 02:Input Status Boolean
Temperature Sensor #4 Failure 02:Input Status Boolean
CAN Serial Number 04:Input Register 32-bit Integer
V1 04:Input Register 32-bit Floating Point
V2 04:Input Register 32-bit Floating Point
V3 04:Input Register 32-bit Floating Point
V4 04:Input Register 32-bit Floating Point
T1 04:Input Register 32-bit Floating Point
T2 04:Input Register 32-bit Floating Point
T3 04:Input Register 32-bit Floating Point
T4 04:Input Register 32-bit Floating Point
I1 04:Input Register 32-bit Floating Point
I2 04:Input Register 32-bit Floating Point
I3 04:Input Register 32-bit Floating Point
I4 04:Input Register 32-bit Floating Point
Table 11. 6I-ADIO Data Points
Name Register Format
CAN Serial Number 04:Input Register 32-bit Integer
I1 04:Input Register 32-bit Floating Point
I2 04:Input Register 32-bit Floating Point
I3 04:Input Register 32-bit Floating Point
I4 04:Input Register 32-bit Floating Point
I5 04:Input Register 32-bit Floating Point
I6 04:Input Register 32-bit Floating Point
0350114-J0 Rev G Page 17